Tips for Energy Conservation for Industries
THERMAL UTILITIES
Boilers
-
Preheat combustion air with waste heat
(22 0C reduction in flue gas temperature increases boiler efficiency by 1%).
-
Use variable speed drives on large boiler combustion air fans with
variable flows.
-
Burn wastes if permitted.
-
Insulate exposed heated oil tanks.
-
Clean burners, nozzles, strainers, etc.
-
Inspect oil heaters for proper oil temperature.
-
Close burner air and/or stack dampers when the burner is off to minimize heat loss
up the stack.
-
Improve oxygen trim control (e.g. -- limit excess air to less than 10% on clean fuels).
(5% reduction in excess air increases boiler efficiency by 1% or: 1% reduction of
residual oxygen in stack gas increases boiler efficiency by 1%.)
-
Automate/optimize boiler blowdown. Recover boiler blowdown heat.
-
Use boiler blowdown to help warm the back-up boiler.
-
Optimize deaerator venting.
-
Inspect door gaskets.
-
Inspect for scale and sediment on the water side
(A 1 mm thick scale (deposit) on the water side could increase fuel consumption by 5 to 8%).
-
Inspect for soot, flyash, and slag on the fire side
(A 3 mm thick soot deposition on the heat transfer surface can cause an increase in fuel consumption to the tune of 2.5%.)
-
Optimize boiler water treatment.
-
Add an economizer to preheat boiler feedwater using exhaust heat.
-
Recycle steam condensate.
-
Study part-load characteristics and cycling costs to determine the most-efficient
mode for operating multiple boilers.
-
Consider multiple or modular boiler units instead of one or two large boilers.
-
Establish a boiler efficiency-maintenance program. Start with an energy audit and
follow-up, then make a boiler efficiency-maintenance program a part of your continuous energy management program.
Steam System
-
Fix steam leaks and condensate leaks
(A 3 mm diameter hole on a pipe line carrying 7 kg/cm2 steam would waste 33 kilo litres of fuel oil per year).
-
Accumulate work orders for repair of steam leaks that can't be fixed
during the heating season due to system shutdown requirements. Tag
each such leak with a durable tag with a good description.
-
Use back pressure steam turbines to produce lower steam pressures.
-
Use more-efficient steam desuperheating methods.
-
Ensure process temperatures are correctly controlled.
-
Maintain lowest acceptable process steam pressures.
• Reduce hot water wastage to drain
-
Fix steam leaks and condensate leaks
-
Remove or blank off all redundant steam piping.
-
Ensure condensate is returned or re-used in the process
(6 0C raise in feed water temperature by economiser/condensate recovery
corresponds to a 1% saving in fuel consumption, in boiler).
-
Preheat boiler feed-water.
-
Recover boiler blowdown.
-
Check operation of steam traps.
-
Remove air from indirect steam using equipment
(0.25 mm thick air film offers the same resistance to heat transfer as a 330 mm thick
copper wall.)
-
Inspect steam traps regularly and repair malfunctioning traps promptly.
-
Consider recovery of vent steam (e.g. -- on large flash tanks).
-
Use waste steam for water heating.
-
Use an absorption chiller to condense exhaust steam before returning the
condensate to the boiler.
-
Use electric pumps instead of steam ejectors when cost benefits permit
-
Establish a steam efficiency-maintenance program. Start with an energy audit and
follow-up, then make a steam efficiency-maintenance program a part of your continuous energy management program.
-
Check against infiltration of air: Use doors or air curtains.
-
Monitor O2 /CO2/CO and control excess air to the optimum level.
-
Improve burner design, combustion control and instrumentation.
-
Ensure that the furnace combustion chamber is under slight
positive pressure.
-
Use ceramic fibres in the case of batch operations.
-
Match the load to the furnace capacity.
-
Retrofit with heat recovery device.
-
Investigate cycle times and reduce.
-
Provide temperature controllers.
-
Ensure that flame does not touch the stock.
Insulation
-
Repair damaged insulation
(A bare steam pipe of 150 mm diameter and 100 m length, carrying saturated steam at 8 kg/cm2 would waste 25,000 litres furnace oil in a year.)
-
Insulate any hot or cold metal or insulation.
-
Replace wet insulation.
-
Use an infrared gun to check for cold wall areas during cold
weather or hot wall areas during hot weather.
-
Ensure that all insulated surfaces are cladded with aluminum
-
Insulate all flanges, valves and couplings
-
Insulate open tanks
(70% heat losses can be reduced by floating a layer of 45 mm diameter polypropylene (plastic) balls on the surface of 90 0C hot liquid/condensate).
Waste heat recovery
-
Recover heat from flue gas, engine cooling water, engine
exhaust, low pressure waste steam, drying oven exhaust,
boiler blowdown, etc.
-
Recover heat from incinerator off-gas.
-
Use waste heat for fuel oil heating, boiler feedwater heating,
outside air heating, etc.
-
Use chiller waste heat to preheat hot water.
-
Use heat pumps.
-
Use absorption refrigeration.
-
Use thermal wheels, run-around systems, heat pipe systems, and air-to-air
exchangers.
ELECTRICAL UTILITIES
Electricity Distribution System
-
Optimise the tariff structure with utility supplier
-
Schedule your operations to maintain a high load factor
-
Shift loads to off-peak times if possible.
-
Minimise maximum demand by tripping loads through a demand
controller
-
Stagger start-up times for equipment with large starting currents to
minimize load peaking.
-
Use standby electric generation equipment for on-peak high load periods.
-
Correct power factor to at least 0.90 under rated load conditions.
-
Relocate transformers close to main loads.
-
Set transformer taps to optimum settings.
-
Disconnect primary power to transformers that do not serve any active loads
-
Consider on-site electric generation or cogeneration.
-
Export power to grid if you have any surplus in your captive generation
-
Check utility electric meter with your own meter.
-
Shut off unnecessary computers, printers, and copiers at night.
Motors
-
Properly size to the load for optimum efficiency.
(High efficiency motors offer of 4 - 5% higher efficiency than standard motors)
-
Use energy-efficient motors where economical.
-
Use synchronous motors to improve power factor.
-
Check alignment.
-
Provide proper ventilation
(For every 10 oC increase in motor operating temperature over recommended peak,
the motor life is estimated to be halved)
-
Check for under-voltage and over-voltage conditions.
-
Balance the three-phase power supply.
(An imbalanced voltage can reduce 3 - 5% in motor input power)
-
Demand efficiency restoration after motor rewinding.
(If rewinding is not done properly, the efficiency can be reduced by 5 - 8%)
-
Properly size to the load for optimum efficiency.
-
Optimise the tariff structure with utility supplier
Drives
-
Use variable-speed drives for large variable loads.
-
Use high-efficiency gear sets.
-
Use precision alignment.
-
Check belt tension regularly.
-
Eliminate variable-pitch pulleys.
-
Use flat belts as alternatives to v-belts.
-
Use synthetic lubricants for large gearboxes.
-
Eliminate eddy current couplings.
-
Shut them off when not needed.
Fans
-
Use smooth, well-rounded air inlet cones for fan air intakes.
-
Avoid poor flow distribution at the fan inlet.
-
Minimize fan inlet and outlet obstructions.
-
Clean screens, filters, and fan blades regularly.
-
Use aerofoil-shaped fan blades.
-
Minimize fan speed.
-
Use low-slip or flat belts.
-
Check belt tension regularly.
-
Eliminate variable pitch pulleys.
-
Use variable speed drives for large variable fan loads.
-
Use energy-efficient motors for continuous or near-continuous operation
-
Eliminate leaks in ductwork.
-
Minimise bends in ductwork
-
Turn fans off when not needed.
Blowers
-
Use smooth, well-rounded air inlet ducts or cones for air
intakes.
-
Minimize blower inlet and outlet obstructions.
-
Clean screens and filters regularly.
-
Minimize blower speed.
-
Use low-slip or no-slip belts.
-
Check belt tension regularly.
-
Eliminate variable pitch pulleys.
-
Use variable speed drives for large variable blower loads.
-
Use energy-efficient motors for continuous or near-continuous operation.
-
Eliminate ductwork leaks.
-
Turn blowers off when they are not needed.
Pumps
-
Operate pumping near best efficiency point.
-
Modify pumping to minimize throttling.
-
Adapt to wide load variation with variable speed drives or
sequenced control of smaller units.
-
Stop running both pumps -- add an auto-start for an on-line
spare or add a booster pump in the problem area.
-
Use booster pumps for small loads requiring higher pressures.
-
Increase fluid temperature differentials to reduce pumping rates.
-
Repair seals and packing to minimize water waste.
- Balance the system to minimize flows and reduce pump power requirements.
• Use siphon effect to advantage: don't waste pumping head with a free-fall (gravity)
return.
Compressors
Compressors
-
Consider variable speed drive for variable load on positive
displacement compressors.
-
Use a synthetic lubricant if the compressor manufacturer permits it.
-
Be sure lubricating oil temperature is not too high (oil degradation
and lowered viscosity) and not too low (condensation
contamination).
-
Change the oil filter regularly.
-
Periodically inspect compressor intercoolers for proper functioning.
-
Use waste heat from a very large compressor to power an absorption chiller or
preheat process or utility feeds.
-
Establish a compressor efficiency-maintenance program. Start with an energy audit
and follow-up, then make a compressor efficiency-maintenance program a part of your continuous energy management program.
Compressed air
-
Install a control system to coordinate multiple air compressors.
-
Study part-load characteristics and cycling costs to determine
the most-efficient mode for operating multiple air compressors.
-
Avoid over sizing -- match the connected load.
-
Load up modulation-controlled air compressors. (They use
almost as much power at partial load as at full load.)
-
Turn off the back-up air compressor until it is needed.
-
Reduce air compressor discharge pressure to the lowest acceptable setting.
(Reduction of 1 kg/cm2 air pressure (8 kg/cm2 to 7 kg/cm2) would result in 9% input
power savings. This will also reduce compressed air leakage rates by 10%)
-
Use the highest reasonable dryer dew point settings.
-
Turn off refrigerated and heated air dryers when the air compressors are off.
-
Use a control system to minimize heatless desiccant dryer purging.
-
Minimize purges, leaks, excessive pressure drops, and condensation accumulation.
(Compressed air leak from 1 mm hole size at 7 kg/cm2 pressure would mean power
loss equivalent to 0.5 kW)
-
Use drain controls instead of continuous air bleeds through the drains.
-
Consider engine-driven or steam-driven air compression to reduce electrical demand
charges.
-
Replace standard v-belts with high-efficiency flat belts as the old v-belts wear out.
-
Use a small air compressor when major production load is off.
-
Take air compressor intake air from the coolest (but not air conditioned) location.
(Every 50C reduction in intake air temperature would result in 1% reduction in
compressor power consumption)
-
Use an air-cooled aftercooler to heat building makeup air in winter.
-
Be sure that heat exchangers are not fouled (e.g. -- with oil).
-
Be sure that air/oil separators are not fouled.
-
Monitor pressure drops across suction and discharge filters and clean or replace
filters promptly upon alarm.
-
Use a properly sized compressed air storage receiver. Minimize disposal costs by
using lubricant that is fully demulsible and an effective oil-water separator.
-
Consider alternatives to compressed air such as blowers for cooling, hydraulic rather
than air cylinders, electric rather than air actuators, and electronic rather than
pneumatic controls.
-
Use nozzles or venturi-type devices rather than blowing with open compressed air
lines.
-
Check for leaking drain valves on compressed air filter/regulator sets. Certain rubber-
type valves may leak continuously after they age and crack.
-
In dusty environments, control packaging lines with high-intensity photocell units
instead of standard units with continuous air purging of lenses and reflectors.
-
Establish a compressed air efficiency-maintenance program. Start with an energy
audit and follow-up, then make a compressed air efficiency-maintenance program a
part of your continuous energy management program.
Chillers
-
Increase the chilled water temperature set point if possible.
-
Use the lowest temperature condenser water available that
the chiller can handle.
(Reducing condensing temperature by 5.5 0C, results in a 20 -
25% decrease in compressor power consumption)
-
Increase the evaporator temperature
(5.50C increase in evaporator temperature reduces compressor power consumption by 20 - 25%)
-
Clean heat exchangers when fouled.
(1 mm scale build-up on condenser tubes can increase energy consumption by 40%)
-
Optimize condenser water flow rate and refrigerated water flow rate.
-
Replace old chillers or compressors with new higher-efficiency models.
-
Use water-cooled rather than air-cooled chiller condensers.
-
Use energy-efficient motors for continuous or near-continuous operation.
-
Specify appropriate fouling factors for condensers.
-
Do not overcharge oil.
-
Install a control system to coordinate multiple chillers.
-
Study part-load characteristics and cycling costs to determine the most-efficient
mode for operating multiple chillers.
-
Run the chillers with the lowest energy consumption. It saves energy cost, fuels a
base load.
-
Avoid oversizing -- match the connected load.
-
Isolate off-line chillers and cooling towers.
-
Establish a chiller efficiency-maintenance program. Start with an energy audit and
follow-up, then make a chiller efficiency-maintenance program a part of your continuous energy management program.
HVAC (Heating / Ventilation / Air Conditioning)
-
Tune up the HVAC control system.
-
Consider installing a building automation system (BAS) or energy
management system (EMS) or restoring an out-of-service one.
-
Balance the system to minimize flows and reduce blower/fan/pump
power requirements.
-
Eliminate or reduce reheat whenever possible.
-
Use appropriate HVAC thermostat setback.
-
Use morning pre-cooling in summer and pre-heating in winter (i.e. -- before electrical
peak hours).
- Use building thermal lag to minimize HVAC equipment operating time.
-
Tune up the HVAC control system.
-
In winter during unoccupied periods, allow temperatures to fall as low as possible
without freezing water lines or damaging stored materials.
-
In summer during unoccupied periods, allow temperatures to rise as high as possible
without damaging stored materials.
-
Improve control and utilization of outside air.
-
Use air-to-air heat exchangers to reduce energy requirements for heating and cooling
of outside air.
-
Reduce HVAC system operating hours (e.g. -- night, weekend).
-
Optimize ventilation.
-
Ventilate only when necessary. To allow some areas to be shut down when
unoccupied, install dedicated HVAC systems on continuous loads (e.g. -- computer
rooms).
-
Provide dedicated outside air supply to kitchens, cleaning rooms, combustion
equipment, etc. to avoid excessive exhausting of conditioned air.
-
Use evaporative cooling in dry climates.
-
Reduce humidification or dehumidification during unoccupied periods.
-
Use atomization rather than steam for humidification where possible.
-
Clean HVAC unit coils periodically and comb mashed fins.
-
Upgrade filter banks to reduce pressure drop and thus lower fan power requirements.
-
Check HVAC filters on a schedule (at least monthly) and clean/change if appropriate.
-
Check pneumatic controls air compressors for proper operation, cycling, and
maintenance.
-
Isolate air conditioned loading dock areas and cool storage areas using high-speed
doors or clear PVC strip curtains.
-
Install ceiling fans to minimize thermal stratification in high-bay areas.
-
Relocate air diffusers to optimum heights in areas with high ceilings.
-
Consider reducing ceiling heights.
-
Eliminate obstructions in front of radiators, baseboard heaters, etc.
-
Check reflectors on infrared heaters for cleanliness and proper beam direction.
-
Use professionally-designed industrial ventilation hoods for dust and vapor control.
-
Use local infrared heat for personnel rather than heating the entire area.
-
Use spot cooling and heating (e.g. -- use ceiling fans for personnel rather than
cooling the entire area).
-
Purchase only high-efficiency models for HVAC window units.
-
Put HVAC window units on timer control.
-
Don't oversize cooling units. (Oversized units will "short cycle" which results in poor
humidity control.)
-
Install multi-fueling capability and run with the cheapest fuel available at the time.
-
Consider dedicated make-up air for exhaust hoods. (Why exhaust the air conditioning
or heat if you don't need to?)
-
Minimize HVAC fan speeds.
-
Consider desiccant drying of outside air to reduce cooling requirements in humid
climates.
-
Consider ground source heat pumps.
-
Seal leaky HVAC ductwork.
-
Seal all leaks around coils.
-
Repair loose or damaged flexible connections (including those under air handling
units).
-
Eliminate simultaneous heating and cooling during seasonal transition periods.
-
Zone HVAC air and water systems to minimize energy use.
- Inspect, clean, lubricate, and adjust damper blades and linkages.
• Establish an HVAC efficiency-maintenance program. Start with an energy audit and
follow-up, then make an HVAC efficiency-maintenance program a part of your
continuous energy management program.
Refrigeration
Refrigeration
-
Use water-cooled condensers rather than air-cooled condensers.
-
Challenge the need for refrigeration, particularly for old batch
processes.
-
Avoid oversizing -- match the connected load.
-
Consider gas-powered refrigeration equipment to minimize electrical
demand charges.
-
Use "free cooling" to allow chiller shutdown in cold weather.
-
Use refrigerated water loads in series if possible.
-
Convert firewater or other tanks to thermal storage.
-
Don't assume that the old way is still the best -- particularly for energy-intensive low
temperature systems.
-
Correct inappropriate brine or glycol concentration that adversely affects heat
transfer and/or pumping energy.
If it sweats, insulate it, but if it is corroding, replace it first.
-
Make adjustments to minimize hot gas bypass operation.
-
Inspect moisture/liquid indicators.
-
Consider change of refrigerant type if it will improve efficiency.
-
Check for correct refrigerant charge level.
-
Inspect the purge for air and water leaks.
-
Establish a refrigeration efficiency-maintenance program. Start with an energy audit
and follow-up, then make a refrigeration efficiency-maintenance program a part of your continuous energy management program.
Cooling towers
-
Control cooling tower fans based on leaving water temperatures.
-
Control to the optimum water temperature as determined from
cooling tower and chiller performance data.
-
Use two-speed or variable-speed drives for cooling tower fan
control if the fans are few. Stage the cooling tower fans with on-off
control if there are many.
-
Turn off unnecessary cooling tower fans when loads are reduced.
-
Cover hot water basins (to minimize algae growth that contributes to fouling).
-
Balance flow to cooling tower hot water basins.
-
Periodically clean plugged cooling tower water distribution nozzles.
-
Install new nozzles to obtain a more-uniform water pattern.
-
Replace splash bars with self-extinguishing PVC cellular-film fill.
-
On old counterflow cooling towers, replace old spray-type nozzles with new square-
spray ABS practically-non-clogging nozzles.
-
Replace slat-type drift eliminators with high-efficiency, low-pressure-drop, self-
extinguishing, PVC cellular units.
-
If possible, follow manufacturer's recommended clearances around cooling towers
and relocate or modify structures, signs, fences, dumpsters, etc. that interfere with air
intake or exhaust.
-
Optimize cooling tower fan blade angle on a seasonal and/or load basis.
-
Correct excessive and/or uneven fan blade tip clearance and poor fan balance.
-
Use a velocity pressure recovery fan ring.
- Divert clean air-conditioned building exhaust to the cooling tower during hot weather.
-
Re-line leaking cooling tower cold water basins.
-
Check water overflow pipes for proper operating level.
-
Optimize chemical use.
-
Consider side stream water treatment.
-
Restrict flows through large loads to design values.
-
Shut off loads that are not in service.
-
Take blowdown water from the return water header.
-
Optimize blowdown flow rate.
-
Automate blowdown to minimize it.
-
Send blowdown to other uses (Remember, the blowdown does not have to be
removed at the cooling tower. It can be removed anywhere in the piping system.)
-
Implement a cooling tower winterization plan to minimize ice build-up.
-
Install interlocks to prevent fan operation when there is no water flow.
-
Establish a cooling tower efficiency-maintenance program. Start with an energy audit
and follow-up, then make a cooling tower efficiency-maintenance program a part of your continuous energy management program.
Lighting
-
Reduce excessive illumination levels to standard levels using
switching, delamping, etc. (Know the electrical effects before doing
delamping.)
-
Aggressively control lighting with clock timers, delay timers,
photocells, and/or occupancy sensors.
-
Install efficient alternatives to incandescent lighting, mercury vapor
lighting, etc. Efficacy (lumens/watt) of various technologies range from best to worst approximately as follows: low pressure sodium, high pressure sodium, metal halide, fluorescent, mercury vapor, incandescent.
-
Select ballasts and lamps carefully with high power factor and long-term efficiency in
mind.
-
Upgrade obsolete fluorescent systems to Compact fluorescents and electronic
ballasts
-
Consider daylighting, skylights, etc.
-
Consider painting the walls a lighter color and using less lighting fixtures or lower
wattages.
-
Use task lighting and reduce background illumination.
-
Re-evaluate exterior lighting strategy, type, and control. Control it aggressively.
-
Change exit signs from incandescent to LED.
DG sets
-
Optimise loading
-
Use waste heat to generate steam/hot water /power an absorption
chiller or preheat process or utility feeds.
-
Use jacket and head cooling water for process needs
-
Clean air filters regularly
-
Insulate exhaust pipes to reduce DG set room temperatures
-
Use cheaper heavy fuel oil for capacities more than 1MW
Buildings
-
Seal exterior cracks/openings/gaps with caulk, gasketing,
weatherstripping, etc.
-
Consider new thermal doors, thermal windows, roofing insulation, etc.
-
Install windbreaks near exterior doors.
-
Replace single-pane glass with insulating glass.
-
Consider covering some window and skylight areas with insulated wall
panels inside the building.
-
If visibility is not required but light is required, consider replacing exterior windows
with insulated glass block.
-
Consider tinted glass, reflective glass, coatings, awnings, overhangs, draperies,
blinds, and shades for sunlit exterior windows.
-
Use landscaping to advantage.
-
Add vestibules or revolving doors to primary exterior personnel doors.
-
Consider automatic doors, air curtains, strip doors, etc. at high-traffic passages
between conditioned and non-conditioned spaces. Use self-closing doors if possible.
-
Use intermediate doors in stairways and vertical passages to minimize building stack
effect.
-
Use dock seals at shipping and receiving doors.
-
Bring cleaning personnel in during the working day or as soon after as possible to
minimize lighting and HVAC costs.
Water & Wastewater
-
Recycle water, particularly for uses with less-critical quality
requirements.
-
Recycle water, especially if sewer costs are based on water
consumption.
-
Balance closed systems to minimize flows and reduce pump
power requirements.
-
Eliminate once-through cooling with water.
-
Use the least expensive type of water that will satisfy the requirement.
-
Fix water leaks.
-
Test for underground water leaks. (It's easy to do over a holiday shutdown.)
-
Check water overflow pipes for proper operating level.
-
Automate blowdown to minimize it.
-
Provide proper tools for wash down -- especially self-closing nozzles.
-
Install efficient irrigation.
-
Reduce flows at water sampling stations.
-
Eliminate continuous overflow at water tanks.
-
Promptly repair leaking toilets and faucets.
-
Use water restrictors on faucets, showers, etc.
-
Use self-closing type faucets in restrooms.
-
Use the lowest possible hot water temperature.
-
Do not use a central heating system hot water boiler to provide service hot water
during the cooling season -- install a smaller, more-efficient system for the cooling
season service hot water.
-
Consider the installation of a thermal solar system for warm water.
-
If water must be heated electrically, consider accumulation in a large insulated
storage tank to minimize heating at on-peak electric rates.
-
Use multiple, distributed, small water heaters to minimize thermal losses in large
piping systems.
- Use freeze protection valves rather than manual bleeding of lines.
-
Consider leased and mobile water treatment systems, especially for deionized water.
-
Seal sumps to prevent seepage inward from necessitating extra sump pump
operation.
-
Install pretreatment to reduce TOC and BOD surcharges.
-
Verify the water meter readings. (You'd be amazed how long a meter reading can be
estimated after the meter breaks or the meter pit fills with water!)
-
Verify the sewer flows if the sewer bills are based on them
Miscellaneous
-
Meter any unmetered utilities. Know what is normal efficient use. Track down causes
of deviations.
-
Shut down spare, idling, or unneeded equipment.
-
Make sure that all of the utilities to redundant areas are turned off -- including utilities
like compressed air and cooling water.
-
Install automatic control to efficiently coordinate multiple air compressors, chillers,
cooling tower cells, boilers, etc.
-
Renegotiate utilities contracts to reflect current loads and variations.
-
Consider buying utilities from neighbors, particularly to handle peaks.
-
Leased space often has low-bid inefficient equipment. Consider upgrades if your
lease will continue for several more years.
-
Adjust fluid temperatures within acceptable limits to minimize undesirable heat
transfer in long pipelines.
-
Minimize use of flow bypasses and minimize bypass flow rates.
-
Provide restriction orifices in purges (nitrogen, steam, etc.).
-
Eliminate unnecessary flow measurement orifices.
-
Consider alternatives to high pressure drops across valves.
-
Turn off winter heat tracing that is on in summer.
0 Comments
Here you can comment and feedback related to BSES Duplicate Bill